Description
Phoenix Contact Monitoring relay for monitoring phase sequence, phase failure and asymmetry, 342…457 V AC, supply from the measurement voltage, 2 changeover contacts
Product type |
Phase monitoring relay |
Operating mode |
100% operating factor |
Mechanical service life |
approx. 2x 107 cycles |
Insulation characteristics |
Insulation |
Basic insulation |
Overvoltage category |
III |
Pollution degree |
2 |
Electrical properties
Service life electrical |
2x 105 cycles at ohmic load, 1000 VA |
Maximum power dissipation for nominal condition |
1 W |
Mains type |
3-phase |
Rated insulation voltage |
300 V |
Rated surge voltage |
4 kV |
Supply |
Supply voltage |
From the measured voltage |
Nominal power consumption |
9 VA |
Input data
Input name |
Measuring input |
Measured value |
AC sine (48 Hz … 63 Hz) |
Nominal input voltage UN |
400 V (3 N ~ 400/230 V) |
Maximum input voltage |
3 N ~ 457/264 V |
Input resistance of voltage input |
15 kΩ |
Frequency range |
48 Hz … 63 Hz |
Setting range for response delay |
≤ 350 ms (fixed setting) |
Setting range for starting delay |
≤ 500 ms (fixed setting) |
Min setting range of the voltage threshold value |
342 V AC |
Max. setting range of the voltage threshold value |
457 V AC |
Function |
Phase sequence |
Phase failure |
Asymmetry |
Asymmetry |
fixed, approx. 30 % |
Recovery time |
< 100 ms |
Output data
Switching |
Contact switching type |
2 floating changeover contacts |
Maximum switching voltage |
250 V AC (in acc. with IEC 60664-1) |
Interrupting rating (ohmic load) max. |
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) |
Output fuse |
5 A (fast-blow) |
Connection data
Connection method |
Screw connection |
Stripping length |
8 mm |
Conductor cross section rigid |
0.5 mm² … 2.5 mm² |
Conductor cross section flexible |
0.25 mm² … 2.5 mm² |
Conductor cross section AWG |
20 … 14 |
Dimensions
Width |
22.5 mm |
Height |
90 mm |
Depth |
113 mm |
Reviews